SecuriSmoke ASD · Product
Compact single-channel aspirating smoke detector
SecuriSmoke ASD 531 is intended for small monitoring areas, individual server racks, clean rooms, false ceilings and other compact protection zones with a short sampling pipe network.

Start with zone structure, pipe complexity, environment, interfaces and destination-market approval—not maximum area alone.
The two data bases below come from different official product materials. Do not combine them into one design.
Usable values depend on the applicable class, topology, hole sizes, pressure, transport time and certificate configuration.
| Alarm sensitivity | 0.02% to 10% obs/m |
|---|---|
| Pre-signal | From 0.006%/m |
| Suction pressure | > 30 Pa |
| Permissible temperature range | -10 °C to +55 °C |
| Protection type / humidity | IP 54 / up to 95% RH, non-condensing |
| Supply voltage | 14 to 30 VDC |
| Typical current consumption | 75 mA at 24 VDC |
| Event memory | 640,000 |
| Programmable relays | 7 |
| Smoke-level display | 3-level LED |
| Dimensions | 195 × 333 × 140 mm |
| Weight | 1.95 kg |
Project rule: published maxima are not construction values. Use the current ASD PipeFlow version and obtain competent destination-market review.
These conditions change sampling performance, transport time and false-alarm control.
Use the project pipe specification and calculate hole diameters, pressure, balance and transport time in the current Securiton ASD PipeFlow software. The maximum pipe value is not a substitute for a calculation.
Sampling holes must be positioned where smoke-laden air will actually pass. Cabinet fan pressure and door-open conditions can change the result and require a functional smoke test.
The detector operating range is -10 °C to +55 °C and up to 95% relative humidity without condensation. Moisture, heavy dust and condensation require project-specific treatment.
Allow accessible space for commissioning, filter replacement and testing. Pipe entry, capillary routing and return-air arrangements must follow the approved project design.
A larger model is not automatically the better model. Choose the clearest compliant structure.
ASD 532 provides a lower pre-signal threshold, higher suction pressure, a wider temperature range and Ethernet connectivity for a medium-sized single-pipe system.
Review ASD 532 ↗FULL SERIESChannels, pipe capability, sensitivity, environment, applications and limitations.
Open comparison ↗An approval mark does not mean automatic acceptance in every country, configuration or fire system.
Confirm the exact certificate, model suffix, approved configuration, current validity and local authority requirement before quotation or design.
Review certificate previews and scope notes →Use the current SECURITON release for final design, ordering and acceptance.
Public answers support first-stage screening; formal confirmation requires project inputs.
ASD 531 is used for small monitoring areas such as individual server racks, small equipment rooms, clean rooms and false ceilings. It is a compact single-channel model, but the sampling network still requires a project-specific PipeFlow calculation.
No. The 800 m² figure belongs to the mainland China product-sheet configuration. An international project must use the applicable approval, EN 54-20 class, local code and a project-specific sampling-pipe calculation.
Consider ASD 532 when the project needs a lower pre-signal threshold, higher suction pressure, a broader operating-temperature range, Ethernet or a longer single-pipe network.
Fact / advice boundary: manufacturer data is presented as fact; model screening and project sequence are PEIEN technical recommendations; final values remain project assumptions until reviewed.