Native technical comparison

ASD 531, ASD 532,
ASD 535-3 or ASD 535-4?

The decisive differences are channel structure, sampling-network capability, environment and interface requirements—not headline area alone.

SECURITON SecuriSmoke ASD selection comparison
Decision factorASD 531ASD 532ASD 535-3ASD 535-4
Typical project scaleSmall, concentrated zones and short networksMedium critical spaces and high-sensitivity single-pipe systemsLarge single zones, long networks, high or low-temperature spacesTwo independent zones or separately calculated networks
Detection channels and structure1 channel / 1 sampling network1 channel / 1 sampling network1 high-performance channel / 1 sampling network2 independent channels / 2 sampling networks
International brochure monitoring area720 m²1,280 m²2,880 m²5,760 m²
Mainland China product-sheet reference800 m²; 80 m; 20 holes1,500 m²; 150 m; 20 holes2,000 m²; 300 m; 60 holes4,000 m²; 600 m; 120 holes
EN 54-20 pipe capability75 m; Class A / B / C holes: 6 / 8 / 12 (Classes A / B / C)120 m; Class A / B / C holes: 8 / 12 / 16 (Classes A / B / C)300 m; Class A / B / C holes: 18 / 56 / 120 (Classes A / B / C)2 × 300 m; Class A / B / C holes: 35 / 112 / 240 total (Classes A / B / C)
Sensitivity and related performanceAlarm 0.02% to 10% obs/m; pre-signal From 0.006%/m; suction > 30 PaAlarm 0.02% to 10% obs/m; pre-signal From 0.002%/m; suction > 100 PaAlarm 0.02% to 10% obs/m; pre-signal From 0.002%/m; suction > 400 PaAlarm 0.02% to 10% obs/m; pre-signal From 0.002%/m; suction > 400 Pa per channel
Environment-10 °C to +55 °C; IP 54; up to 95% RH, non-condensing-20 °C to +60 °C; IP 54; up to 95% RH, non-condensing-30 °C to +60 °C; IP 54; up to 95% RH, non-condensing-30 °C to +60 °C; IP 54; up to 95% RH, non-condensing
Interfaces and networkingNo PC connection; No network interfaceEthernet; RS-485 and EthernetUSB; Optional RS-485; no native EthernetUSB; Optional RS-485; no native Ethernet
On-board event memory1,000 events on board1,000 events on board430 events on board430 events on board
Recommended applicationsIndividual server racks, Small equipment rooms, Clean rooms, False ceilingsData rooms, Clean rooms, Laboratories, Telecommunications facilitiesLarge data centres, High-bay storage, Deep-freeze warehouses, Large or high hallsLarge data centres, Two-zone protection, Large logistics facilities, Critical infrastructure
Main limitationsNot intended for long, two-zone or below -10 °C projects; no ASD 532 Ethernet capability.Not intended for two independent channels, very large networks or below -20 °C environments.One independent channel; not a substitute when two zones require separate judgement.Usually excessive for a small single zone; both channels require separate calculation and identification.
Inputs required before selectionConfirm short-network fit and interface, display and temperature requirements.Provide HVAC states, return-air / room strategy and integration requirements.Confirm one large independent zone; provide long-network, low-temperature and contamination conditions.Define two zone boundaries, two PipeFlow models, power and independent alarm logic.
Official sourceSECURITON SecuriSmoke ASD Product Brochure V2.0 EN, document 831055 10.25; Product Manual V2606 for separately labelled mainland China valuesSECURITON SecuriSmoke ASD Product Brochure V2.0 EN, document 831055 10.25; Product Manual V2606 for separately labelled mainland China valuesSECURITON SecuriSmoke ASD Product Brochure V2.0 EN, document 831055 10.25; Product Manual V2606 for separately labelled mainland China valuesSECURITON SecuriSmoke ASD Product Brochure V2.0 EN, document 831055 10.25; Product Manual V2606 for separately labelled mainland China values

A candidate model becomes a project decision only after destination-market approval review, a current ASD PipeFlow report and competent fire-strategy coordination.

Selection questions

Direct answers for the first screening step.

What is the key difference between ASD 531 and ASD 532?

ASD 532 offers a lower pre-signal threshold, higher suction pressure, a wider temperature range, a 10-level display and network interfaces. ASD 531 is suited to compact, short-network projects.

How should ASD 535-3 and ASD 535-4 be selected?

Use ASD 535-3 when one independent channel satisfies the project. Evaluate ASD 535-4 when two zones require independent sampling, indication or control.

Can a model be selected by maximum area?

No. Approval, class, pipe length, holes, transport time, airflow, environment, interfaces and maintenance must also be satisfied in a project-specific calculation.

Turn the comparison into a project decision.

Submit the application, protection area, environmental conditions, pipe-network information, destination market and project stage.

Request selection review ↗