China configuration reference
- Monitoring area
- 4,000 m²
- Sampling pipe
- 400 m
- Sampling holes
- 60
- Farthest hole
- 110 m per channel
SecuriSmoke ASD · Product
High-performance two-channel aspirating smoke detector
SecuriSmoke ASD 535-4 provides two independent detection channels for two protection zones, extensive spaces and separately calculated sampling networks in demanding applications.

Start with zone structure, pipe complexity, environment, interfaces and destination-market approval—not maximum area alone.
The two data bases below come from different official product materials. Do not combine them into one design.
Usable values depend on the applicable class, topology, hole sizes, pressure, transport time and certificate configuration.
| Alarm sensitivity | 0.02% to 10% obs/m |
|---|---|
| Pre-signal | From 0.002%/m |
| Suction pressure | > 400 Pa per channel |
| Permissible temperature range | -30 °C to +60 °C |
| Protection type / humidity | IP 54 / up to 95% RH, non-condensing |
| Supply voltage | 10.5 to 30 VDC |
| Typical current consumption | 260 to 290 mA at 24 VDC |
| Event memory | 16,000,000 |
| Programmable relays | 13 |
| Smoke-level display | 2 × 10-level LED |
| Dimensions | 265 × 397 × 146 mm |
| Weight | 4.1 kg |
Project rule: published maxima are not construction values. Use the current ASD PipeFlow version and obtain competent destination-market review.
These conditions change sampling performance, transport time and false-alarm control.
Each channel requires its own PipeFlow model and verification of hole sizes, pressure, transport time and balance. A combined total does not override the limit of either channel.
Two channels can protect separate zones, but alarm, isolation, fault and fire-system interface logic must be defined in the overall fire strategy.
The detector operating range is -30 °C to +60 °C and up to 95% relative humidity without condensation. Heavy dust, moisture and deep-freeze conditions require appropriate pre-treatment.
Confirm simultaneous two-channel power demand, interface capacity, accessible maintenance space and permanent pipe identification to prevent cross-connection during service.
A larger model is not automatically the better model. Choose the clearest compliant structure.
ASD 535-3 is the single-channel configuration and is usually more efficient when one independently calculated network meets the zoning requirement.
Review ASD 535-3 ↗FULL SERIESChannels, pipe capability, sensitivity, environment, applications and limitations.
Open comparison ↗An approval mark does not mean automatic acceptance in every country, configuration or fire system.
Confirm the exact certificate, model suffix, approved configuration, current validity and local authority requirement before quotation or design.
Review certificate previews and scope notes →Use the current SECURITON release for final design, ordering and acceptance.
Public answers support first-stage screening; formal confirmation requires project inputs.
No. It is the mainland China two-channel product-sheet configuration. Each channel and every international project must be evaluated separately against the applicable approval, topology and PipeFlow result.
Yes, this is a typical use case, provided each channel independently satisfies the pipe calculation, zoning, alarm interface and destination-market approval requirements.
No. ASD 535-4 is appropriate when two independent channels are required. If one channel meets the protection and calculation requirements, ASD 535-3 is generally simpler to design, commission and maintain.
Fact / advice boundary: manufacturer data is presented as fact; model screening and project sequence are PEIEN technical recommendations; final values remain project assumptions until reviewed.
Last reviewed: 27 July 2026 by the PEIEN technical content team. Project-level review must be completed by a suitably qualified fire professional or an ASD practitioner with relevant project experience.